They have their own specific setup that I can’t remember (too many schematics in my brain). If it runs for a little bit and then shuts off for a while, kicks on for a bit and yada yada, check your condensate line, might be tripping a “safety switch.” Thats a quick fix, vacuum out the line. Check around the condenser and see if there’s a bunch of droppings. Rodents like to keep warm and chew on wires, those little bastards. Could be a number of things. But I’d start with the condy line. Answer from Deleted User on reddit.com
🌐
JustAnswer
justanswer.com › hvac › bvmqb-u4-error-daikin-indoor-unit-keeps.html
Daikin U4 Error Code: Expert Solutions and Fixes
December 27, 2018 - If the U4 error persists and there are no apparent wiring problems, it may indicate a malfunctioning communication module on the board, and it would be advisable to consult a service technician for further troubleshooting.
🌐
Star-supply
star-supply.com › content › Daikin Single- Multi -U4 Error Code.pdf pdf
Daikin Single-Multi U4 Error Codes
If correct voltage is present on the outside wire, reconnect the wire and turn on the unit. If the U4 error still
Discussions

I have a Daikins inverter that is giving a U4 error code. I
I have 3 aircons and all inverters and are showing error code U4 Daikin. FTXN60LV1B and FTX35JV1B. So what is happening ... Members enjoy round-the-clock access to 12,000+ verified Experts, including doctors, lawyers, tech support, mechanics, vets, home repair pros, more. More on justanswer.com
🌐 justanswer.com
1
August 3, 2024
[Daikin VRV] [220 VAC] U4-01 Error Code Help
They have their own specific setup that I can’t remember (too many schematics in my brain). If it runs for a little bit and then shuts off for a while, kicks on for a bit and yada yada, check your condensate line, might be tripping a “safety switch.” Thats a quick fix, vacuum out the line. Check around the condenser and see if there’s a bunch of droppings. Rodents like to keep warm and chew on wires, those little bastards. Could be a number of things. But I’d start with the condy line. More on reddit.com
🌐 r/hvacadvice
6
4
September 6, 2024
Daikin support. my air/con heater got the error code U4-01
Daikin indoor unit - CTXS09HVJU - Error Code U4. A few days ago. Other units in same space working fine. This one used ... Members enjoy round-the-clock access to 12,000+ verified Experts, including doctors, lawyers, tech support, mechanics, vets, home repair pros, more. More on justanswer.com
🌐 justanswer.com
1
December 22, 2022
Daikin Mini split- error code U4
There’s a specific process to it. Need a Daikin d checker tool to really further diagnose More on reddit.com
🌐 r/hvacadvice
7
2
November 25, 2023
🌐
ADK Kooling
adk.co.uk › home › air conditioning › daikin error code u4 — vrv communication fault explained
Daikin Error Code U4 | Communication Fault Fix | ADK London
March 23, 2026 - U4 is the Daikin VRV error code we see most often, and it’s typically resolved on the first visit. Our engineers carry replacement PCBs for common Daikin indoor and outdoor units, along with the manufacturer’s diagnostic interface to interrogate ...
Price   $$
Address   Daneshill House, 3 Waterloo Road, UB8 2QX, Uxbridge
🌐
AirReps
airreps.com › 2025 › 11 › understanding-the-u4-error-code-in-daikin-vrv-systems
Understanding the U4 Error Code in Daikin VRV Systems - AirReps
November 19, 2025 - A U4 error code almost always requires professional service. A qualified VRV technician will have the proper tools to test communication signals, measure voltages, and diagnose which component is causing the failure.
🌐
JustAnswer
justanswer.com › hvac › pphzc-daikins-inverter-giving-u4-error-code.html
Daikin Inverter U4 Error Code? Expert Troubleshooting Guide
August 3, 2024 - ... Inverter systems often face sensor faults and communication errors causing startup failure. The U4 error on a Daikin inverter typically indicates a communication or sensor fault.
🌐
Reddit
reddit.com › r/hvacadvice › [daikin vrv] [220 vac] u4-01 error code help
r/hvacadvice on Reddit: [Daikin VRV] [220 VAC] U4-01 Error Code Help
September 6, 2024 -

My air conditioning failed on me some time today when I was at work, and when I returned home it was 92° inside my home. Figures this would happen during the (hopefully) hottest week of the year in Los Angeles. This system was professionally installed in June of 2020, and has worked without issue until now. The company that did it was bought out by another larger firm, and they are unable to send a tech out for another 17 days. I’m kind of SOL there. I change the filters every six months in the air handlers, and regularly hose down/clean the exterior unit. With a basic visual inspection, it does not appear that there are any blockages/impediments to air flow. I have tried powering off both the exterior unit and both interior air handlers by switching off the breakers on two separate occasions. The cooling works for about 10 minutes and then the error message is displayed again on the interior control panel. Any ideas?

🌐
Daikin
daikin.com › products › ac › services › error_codes
Error Codes | After Sales Service | Air Conditioning and Refrigeration | Daikin Global
Error Code Search offers information on the cause of the malfunction and the status of your air conditioner by entering the error code.
Find elsewhere
🌐
JustAnswer
justanswer.com › hvac › kv8uf-daikin-support-air-con-heater-error-code-u4-01.html
Daikin U4-01 Error Code? Troubleshooting Help & Fix Guide
December 22, 2022 - Daikin indoor unit - CTXS09HVJU - Error Code U4. A few days ago. Other units in same space working fine. This one used ... Members enjoy round-the-clock access to 12,000+ verified Experts, including doctors, lawyers, tech support, mechanics, vets, home repair pros, more.
🌐
Reddit
reddit.com › r/hvacadvice › daikin mini split- error code u4
r/hvacadvice on Reddit: Daikin Mini split- error code U4
November 25, 2023 -

I’m a little lost on trying to trouble shoot this one, any advice is appreciated. I purchased a 2 ton single head Daikin minisplit system online a few months ago to install in a workshop in my backyard, that I’m in the process of renovating. Everything was going smoothly with the install, doing the majority of the work myself. I am a builder by trade and have done several minisplit installs over the years. I hired an HVAC tech to connect the refrigerant linesets, and evacuate/ pressure test the lines. As far as I can tell the problem came about when I connected the wiring. Unfortunately I crossed the signal line and one of the power lines at the outdoor unit control wiring. When I went to fire up the system, the indoor unit status light started flashing blue, indicating a system error. I realized what had happened then and corrected the wiring. No luck, still flashing blue. Error code retrieval at this point, at the remote control reads U4: communication error. Next I tried pulling the outdoor unit control panel to see if there is a blown fuse. I was able to locate 3 separate fuses but none of them tested bad. Pulled the indoor unit control board and there is one fuse which also checked out ok. Last I try running a separate jumper wire externally to eliminate the possibility that there is an unseen break in the original signal wire. I then try turning the system on again, same thing: indoor unit status light flashing blue and error code U4. Any ideas?

🌐
Silverback Air-con
silverbackaircon.sg › home › aircon error code › daikin error code › ultimate guide to daikin u4 error code
Ultimate Guide to Daikin U4 Error Code - Silverback Air-con
October 28, 2025 - Is your Daikin system displaying the dreaded U4 error code? Learn how to resolve this issue with our ultimate guide to Daikin U4 error code.
🌐
Beaconsaves
beaconsaves.com › blog › daikin-mini-split-u4-error-code
Daikin Mini Split U4 Error Code: What It Means & What to Check | Beacon Services & Appliances
That is not a homeowner-safe repair area. Avoid removing covers or tightening live terminals. ... Our friendly technicians in yellow usually confirm proper power first, then verify communication wiring, terminal integrity, polarity and continuity where applicable, and whether one control board has stopped sending or receiving the expected signal. If U4 returns after one reset, professional diagnosis is the best move. Communication errors rarely resolve by themselves, and repeated power cycling usually does not fix the root cause.
🌐
Airway Group
airway-group.co.uk › home › help & advice › daikin air conditioning fault codes explained [infographic]
Daikin Air Conditioning Fault Codes Explained [Infographic] | Airway
April 2, 2026 - UA – Combination error of indoor/BS/outdoor unit, setting error of PCB at site – There is an incorrect combination of indoor, BS or outdoor units (the wrong quantity or models, for example). If you’re in the Cambridge area, our locally based air-conditioning engineers can fix the issue the same day. Further afield? Book a Daikin repair service or just contact us.
🌐
Airchillac
airchillac.com › daikin-ac-error-codes
Daikin AC Error Codes Guide – Fixes, and Troubleshooting Tips | AirChill AC Maintenance and Duct Cleaning
June 5, 2025 - If your Daikin AC shows error code A1, the main board inside the indoor unit might not be working. ... A professional may need to replace the control board. Error code U4 means the indoor and outdoor units are not connected properly.
🌐
HVAC In Expert
hvacinexpert.com › home › daikin ac error codes list
Daikin AC Error Codes List
April 14, 2026 - Whether it’s U4 communication error, A5 high pressure, or L5 compressor fault, understanding the meaning and causes allows you to take the right action. Regular maintenance and professional servicing ensure your Daikin AC runs efficiently for years. If error persists, always contact authorized Daikin service center for safe and reliable repair...
🌐
HVAC Toolkit
hvactoolkit.org › home › resources › error codes › daikin
Daikin Error Codes - Complete Fault Code List & Solutions | HVAC Toolkit
Complete Daikin error code list for mini-splits, VRV systems, and air conditioners. Find meanings, causes, and troubleshooting solutions for all Daikin fault codes.
🌐
Daikin
my.daikin.eu › content › dam › DASW › supportavdelningen › Felkoder_SM-TS3errorcode_chart.pdf pdf
Simple Self-Diagnosis by Malfunction Code After Sales Service Division (SM-TS3)
“long beep” sound are error code. 8. Press the MODE button to exit from the · diagnosis mode. The display “ ” means the trial operation · mode. 9. Press the ON/OFF button twice to return · to the normal mode. Note: When the remote controller is left untouched · for 60 seconds, it returns to the normal mode. No. 1 · 2 · 3 · 4 · 5 · 6 · 7 · 8 · 9 · 10 · 11 · Code · 00 · U4 ·
Top answer
1 of 2
7
Hello, and thank you for your question. I will be here to assist you with your inquiry today. It's important for us to collaborate as a team to address this issue or at least find a way to troubleshoot it and get you sorted out. If you haven't accepted my help by clicking the accept button on your screen after I provide an answer, I will need to move on to assist others who are seeking genuine paid support. Please remember that this service is not free, and experts are compensated only upon your acceptance. You can always request more information and ask questions, even after accepting my assistance; this is not a problem. The code U4 indicates a communication error between the indoor and outdoor units. The code UF signifies a more serious communication fault between the indoor and outdoor units. Try turning it off at the mains for an hour, and then try again. If that doesn't work, Daikin offers a 5-year warranty on their AC systems, so please contact them as soon as possible. Daikin service centres Fault code sheet: To repair, you will need to determine which of the two motherboards is faulty and replace it, or replace the cable that connects the two components if both boards are functioning properly.I assume you can handle this since you were already aware of the other information I provided, so you won't need me to explain how it's done.To answer your question directly, there is no quick fix, as a component has failed, and without the necessary parts, you won't be able to change and test anything.Cheers and happy holidays.
2 of 2
7
Hello, and thank you for your question. I will be here to assist you with your inquiry today. It's important for us to collaborate as a team to address this issue or at least find a way to troubleshoot it and get you sorted out. If you haven't accepted my help by clicking the accept button on your screen after I provide an answer, I will need to move on to assist others who are seeking genuine paid support. Please remember that this service is not free, and experts are compensated only upon your acceptance. You can always request more information and ask questions, even after accepting my assistance; this is not a problem. The code U4 indicates a communication error between the indoor and outdoor units. The code UF signifies a more serious communication fault between the indoor and outdoor units. Try turning it off at the mains for an hour, and then try again. If that doesn't work, Daikin offers a 5-year warranty on their AC systems, so please contact them as soon as possible. Daikin service centres Fault code sheet:
🌐
Reddit
reddit.com › r/hvac › daikin mini split u4 error
r/HVAC on Reddit: Daikin Mini Split U4 Error
August 14, 2025 -

I’ll try to keep this as brief as possible, I’m trying to resolve a U4 code on a single zone RXL09QMVJU, I do not currently have the model handy on the indoor unit. I know the system is old but I’m with one of the few companies in my area that actually repairs things unless a replacement is absolutely necessary.

I’ve been on the phone twice with Daikin tech support, I’ve run through all of the diagnostic procedures they’ve given me so far and even run through others that shouldn’t throw this particular code. At this point both indoor and outdoor boards have been replaced and I’m starting to question if I might have a board that was DOA when I installed it.

Indoor unit turns on, will run on fan mode but any mode that would involve the compressor errors out, I have proper ac voltage to everything, per their procedure Daikin says I should be looking for 53-55v dc at the indoor board from terminal 3 to ground with the communications wire disconnected. I have 75v dc, I also have the sister unit ten feet away in the next room running fine with 75v dc at that indoor board.

Outdoor board sends no voltage to the compressor, fan was ohmed out and fine, emergency cooling runs the indoor unit at full capacity but again outdoor unit doesn’t run at all and I have continuity in the wiring between indoor and outdoor units.

I’ve been getting some inconsistent information from Daikin between the manuals and talking to them so I figured I’d ask here for opinions.