Ducted under floor residential system, 8 zone controller and 11 outlets. We have been having an E3 error for nearly a year: “E3: Fault Code E3: Actuation of high pressure switch (HPS).”
The installation company has been very responsive, but have not fixed the issue even though they have replaced almost everything:
-control board -intake duct -high pressure switch -high pressure sensor -second intake was added to a different part of the house -completely drained and replaced refrigerant multiple times
The only common cause is when we have a cold night, not necessarily freezing cold but below 40 F / 5c. Doesn’t seem to happen as frequently on mild nights.
Has anyone experienced something like this? What would be left to even replace? I am equally annoyed and curious to know what is actually causing it!