I recently got a very good deal on a VERTIV Liebert GXT5-1500LVRT2UXL UPS. I am trying to get it setup with NUT so it can gracefully shutdown my equipment. This is my first time working with NUT. Before this I just let my UPS go until there is no more power and then cut power to my systems (Which is NOT good for them).
This device connects via USB to my NAS (Running Truenas Scale Community 25.04) which I would like to act as the master for NUT. The UPS is not being detected by NUT but is visible in lsusb.
I have tried to use the usbhid-ups driver and have manually set the port to /dev/hidraw0 (Where the UPS is mounted) with no success.
Any advice on anything else I can try to get this UPS working?
UPDATE 1: I just found this comment from about a year ago which indicates the NUT support for this brand is a ongoing issue. I also agree that even though this UPS is very nice the fan noise is a issue for a office environment. Given this brand does not have many records in the NUT Hardware compatibility list I suspect supporting NUT is not a priority for VERTIV Liebert.
UPDATE 2: u/Outrageous_Ad_3438 gave some good solutions that I am going to take a look at for my setup. I am going to mark this as solved.
Main takeaway from this is this UPS does NOT support NUT but can be used with the Vertiv Power Assist software running on a different computer and using a script or custom software on that system pretend to be a NUT master and shutdown the NAS.